Home

href="
AIR FILTER MONITOR  
INSTALLATION AND  
SETUP OPTIONS  
The Air Filter Monitor counts the number of days, and the amount of usage since  
your filter has been replaced. In Run mode, the CHANGE FILTER indicator will  
appear when the remaining filter days have reached zero and the filter should be  
changed. To set and use the Air Filter Monitor, turn the rotary dial to AIR FILTER.  
Press NEXT and the Filter Days Left value will start flashing. Use the UP or DOWN  
buttons to select the number of days of filter life that your filter is rated for. Setting  
this value to OFF will disable the filter monitor. Return the dial to the RUN position  
once you are finished setting the filter life. To monitor the Filter Days Left or Filter  
Percent Left, turn the dial to the AIR FILTER position. The amount of filter life  
remaining will be shown in the clock portion of the display screen. Return the dial  
to the RUN position once you are finished viewing the filter life remaining.  
OPERATING INSTRUCTIONS  
Install two new Energizer® or DURACELL® "AA"  
size alkaline batteries before continuing further.  
Ensure that the batteries are installed in the  
proper direction as per the markings shown in  
the battery tray.  
TX500E Programmable Thermostat  
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only.  
Energizer® is a registered trademark of Eveready Battery Company, Inc.  
DURACELL® is a registered trademark of The Gillette Company, Inc.  
BATTERYY CCOOMMPPAARRTTMMEENNTT  
BATTERY COMPARTMENT  
NOTE:  
All of the settings, options, and components listed in this section are located on the  
rear of the thermostat, on the circuit board.  
Mt. Laurel, New Jersey 08054, USA  
52024  
RESET FILTER COUNTER  
HARDWARE RESET  
Once you have replaced your filter, the filter life counter is reset back to its full  
amount remaining value by turning the dial to AIR FILTER and pressing the UP and  
DOWN buttons together at the same time. NOTE: The counter is also reset by  
changing the filter setting value, as described above, to a different number of days.  
Thank you for your confidence in our product. To obtain the best results from your  
investment, please read these instructions and acquaint yourself with your  
purchase.  
The hardware reset is a push button that is located on the right edge of the circuit  
board, just above the battery location. This reset button is used by the thermostat  
to reset the unit’s clock, and read the position of all of the option switches. When  
any of the following items are changed, the hardware reset button must be pushed  
for the change to be recognized. User temperature programs are not erased when a  
hardware reset is performed.  
COMPATIBILITY  
ADVANCED FEATURES  
This thermostat can be used with most single stage 24 volt: gas, oil or electric  
heating and/or cooling systems, single stage heat pumps, or gas Millivolt heating  
systems. It cannot be used with 3-wire zone valves, 120 volt heating systems, or  
multi-stage heat pumps. Ask your dealer for other LUX thermostats to control those  
systems.  
JP1  
FAN  
SWING SETTING  
FURNACE MODE  
A thermostat works by turning your heating or cooling system on and off whenever  
the room temperature varies from the set-point temperature. The amount of this  
variation is called the “swing.” Your system should cycle on about 3 to 6 times per  
hour. A smaller swing number increases the number of cycles per hour, so the  
room temperature is more precise and constant. A larger swing number decreases  
the number of cycles per hour, but saves energy in most cases. To change the  
Swing setting, turn the dial to RUN mode. Hold down the NEXT button and push the  
HOLD button once, then let go of both. The words SWING and SET will appear on  
the screen with a number. Use the UP/DOWN buttons to change the number value  
between 1 and 9. Number 1 is the default setting. Press the NEXT button to accept  
the setting and return to normal Run mode.  
This is a plastic jumper cap which  
can be in one of two positions,  
GAS or ELECTRIC.  
ELECTRIC  
GAS  
FEATURES  
LCD - Liquid Crystal Display  
Set Temperature Buttons  
Fan Mode  
The Furnace Mode setting determines how the thermostat controls the fan  
operation. This setting has no effect in Cool Mode. While in Heat Mode, with the  
jumper in the Gas position, the fan is controlled by your furnace. With the jumper  
in the Electric position, the fan is controlled by the thermostat and is turned on  
when the heating terminal becomes energized.  
TU  
Switch  
DAY  
HEAT  
FAN  
PM  
:
Software  
Reset Button  
5 36 72  
Temperature  
Mode Switch  
The following option settings are all located within a group of small switches  
labeled 1 through 3 as shown below, and are located in the center of the circuit  
board.  
WEEKEND  
PROGRAM  
TEMPERATURE CALIBRATION  
FAN  
TEMERATURE  
HEAT  
WEEKDAY  
PROGRAM  
RESET  
AUTO  
ON  
The internal temperature sensor in this thermostat is accurately calibrated at the  
factory. The Temperature Calibration feature allows you to manually offset the  
measured temperature by as much as plus or minus 5°F (3°C) degrees from its  
original value. This feature can be useful to match this thermostat to another one  
or more, if multiple thermostats are used in the same home. To change the  
Temperature Calibration, turn the dial to RUN mode, and place the Temperature  
mode switch in the OFF position. Hold down the UP button and push the DOWN  
button once, then let go of both. The words CAL and SET will appear on the screen  
with a number. Use the UP/DOWN buttons to change the number value between -  
5°F (-3°C) and +5°F (+3°C) degrees. 0 degrees of correction is the default setting.  
Press the NEXT button to accept the setting and return to Run mode.  
OFF  
COOL  
NEXT  
R U N  
SET  
LUX  
DAY/TIME  
Quick Reference  
Door Instructions  
HOLD  
LUX  
AIR FILTER  
TX500E  
Speed  
Dial®  
Small elegant design  
• 12/24 Hr Clock Display  
Exclusive LUX Speed Dial®  
Air Filter Monitor  
Adjustable Temperature Differential /  
Cycle Rate  
User Temperature Offset /  
Calibration  
5 Minute Minimum Run/Off Time For  
Short Cycle and Compressor  
Protection  
TIME FORMAT  
This determines how the thermostat displays the clock and all other times on the  
screen. Switch position OFF is 12 HR, and ON is 24 HR.  
5-2 Day Programming  
Energy Star Compliant  
4 Periods Per Day  
KEYLOCK  
TEMPERATURE SCALE  
This determines how the thermostat displays all temperatures on the screen.  
Switch position OFF is F°, and ON is C°.  
To prevent tampering with any of your settings or temperatures, most of the front  
panel buttons can be locked out by pressing the following four-button sequence:  
NEXT, NEXT, NEXT, HOLD. This sequence of keys will lock and also unlock these  
items: UP, DOWN, NEXT, HOLD, the Rotary Dial, and the Software Reset button.  
Neither of the Mode slide switches are locked out. When the Keylock is activated, a  
padlock icon will be visible in the area above the clock as shown below.  
Battery Free Memory Storage  
Temporary Temperature Override  
Temperature Hold  
Keyboard Lockout  
FILTER DISPLAY  
F/C Temperature Display  
This determines how the remaining filter life will be displayed when the rotary dial  
is turned to the AIR FILTER position. In the Percent (%) mode, the display will  
count down the percentage of air filter life remaining before a filter change is  
recommended. In the Days mode, the display will count down the number of  
calendar days remaining before a filter change is recommended. Switch position  
OFF is Percent mode, and ON is Days mode.  
INSTALLATION  
T
U
Please read ALL of these instructions carefully before beginning installation.  
Save them for future reference.  
D
AY  
HEAT  
PM  
:
5 36  
72  
TOOLS REQUIRED  
FRONT PANEL ITEMS  
SOFTWARE RESET  
The software reset is a small recessed push button that is located right above the  
NEXT button. This button can be pushed with a pencil or the end of a paper clip.  
This reset clears all of the heating and cooling programs, filter settings, and other  
user changeable preferences to their default values. You should write down your  
heating and cooling program times and temperatures prior to using the software  
reset.  
NOTE:  
#1 Phillips screwdriver  
Drill with 3/16 in. (4.8mm) bit  
Wire Stripper / Cutter  
The Keylock will be disabled if the Hardware Reset button is pressed.  
PROGRAMMING  
CAUTION: This thermostat is protected against normal minor static electric  
discharges, however to minimize the risk of damaging the unit in extremely dry  
weather, touch a grounded metal object before touching your thermostat.  
For all of the programming areas that are described below, this thermostat provides  
four independent periods per day for Heat mode and Cool mode, they are: MORN,  
DAY, EVE, and NITE. Each period ends at the start time of the following period. The  
programs for each Temperature mode are programmed separately. When you  
perform a Software Reset, an Energy Star® approved program is inserted into all of  
the program periods. You can use these default programs or alter any portion of  
them to suit your own preferences. When setting the program items, the value that  
is flashing is the item that you can change at that time.  
LOCATION  
On replacement installations, mount the new thermostat in place of the old one  
unless the conditions listed below suggest otherwise. On new installations, follow  
the guidelines listed below.  
1. Locate the thermostat on an inside wall, about 5 ft. (1.5m) above the floor, and  
in a room that is used often.  
2. Do not locate where air circulation is poor, such as in a corner or an alcove, or  
behind an open door.  
MODE SWITCHES  
There are two mode switches on the front, a Temperature mode switch and a Fan  
mode switch. The Temperature mode switch has three positions: HEAT, OFF, and  
COOL. In the winter, set the system switch to HEAT to control your heating system.  
In the summer, set the switch to COOL to control your air conditioner. In the spring  
and fall or when the windows are open, you can set the switch OFF. The Fan mode  
switch has two positions, AUTO and ON. Setting the Fan mode switch to AUTO,  
automatically runs your system's blower fan as required only during heating and  
cooling activation. Setting the Fan mode switch to ON, runs your system’s fan  
continuously, even if heating or cooling is not needed, including when the  
Temperature mode switch is in the OFF position to provide air circulation only.  
SET WEEKDAY PROGRAM  
Select either HEAT or COOL with the Temperature mode switch. Rotate the dial to  
WEEKDAY PROGRAM. You will be programming all five weekdays at the same time.  
The first period is MORN. Using the UP and DOWN buttons, set the start time for  
this period, and then push the NEXT button to proceed. Now set the desired set  
temperature for the MORN period using the UP and DOWN buttons, and push NEXT  
to proceed. Now set the start time and set temperature for the DAY period,  
pushing NEXT after each to advance. Continue with these same steps to set the  
start time and set temperature for the EVE, and NITE program periods. When you  
are finished setting all four periods, you may continue pushing the NEXT button  
through all four periods to review your entries, or turn the dial to RUN if you are  
finished. These same programming steps for all four periods must be performed in  
both Heat and Cool Temperature modes independently.  
3. Do not install it where there are unusual heating conditions, such as: in direct  
sunlight; near a lamp, television, radiator, register, or fireplace; near hot water  
pipes in a wall; near a stove on the other side of a wall.  
4. Do not locate in unusual cooling conditions, such as: on a wall separating an  
unheated room; or in a draft from a stairwell, door, or window.  
5. Do not locate in a damp area. This can lead to corrosion that may shorten  
thermostat life.  
NOTE:  
The Fan mode switch only works if your system provides a wire for the  
thermostat’s “G” wire terminal.  
6. If painting or construction work has yet to be completed, cover the unit  
completely or do not install it.  
WARNING:  
PUSH BUTTONS  
Read instructions carefully before removing any wires from your existing  
There are four primary push buttons on the front of the thermostat: The UP and  
DOWN arrow keys, the NEXT button, and the HOLD button.  
thermostat.  
SET WEEKEND PROGRAM  
Do not short (jumper) across the electric terminals on the furnace or air  
Turn the dial to WEEKEND PROGRAM. You will be programming both Saturday and  
Sunday at the same time. You will begin with the start time of the MORN period,  
and use the same procedures that were performed while setting the Weekday  
Program periods, using the NEXT button to advance through the values. Return the  
dial to the RUN position when you are finished.  
conditioner to test the system. This may damage the thermostat and void your  
warranty.  
ROTARY DIAL  
The LUX Speed Dial® provides an easy way to quickly navigate between the different  
programming areas. This rotary dial has five individual positions.  
This thermostat should be limited to 1.5 amps per terminal, and a maximum  
of 2 amps total; higher current than this may cause damage to the thermostat.  
All wiring must conform to the local codes and ordinances that are in your  
particular location.  
OPERATING INSTRUCTIONS  
SET DAY/TIME  
Rotate the dial to the SET DAY/TIME position. You should see the word SET appear  
on the display, along with the clock and a day of the week that is flashing. With the  
day flashing, press the UP button to advance the day to the desired day. Press the  
NEXT button, this should cause the time to start flashing and the day to remain on  
steady. Using either the UP or DOWN buttons, adjust the clock to the desired time.  
The clock digits will increment rapidly if either the UP or DOWN buttons are held in  
the pressed position.  
Your thermostat is a precision instrument, please handle it with care to avoid  
BATTERIES AND MAINTENANCE  
damage.  
This thermostat can be powered either by “AA” alkaline batteries, by 24VAC system  
common power, or a combination of both. If you are using batteries alone, the  
batteries should be replaced AT LEAST once per year, or sooner if the LOW BAT  
battery symbol appears in the lower left  
portion of the display screen as shown  
below.  
REMOVAL OF OLD UNIT  
1. Turn OFF the electricity to all heating and cooling components.  
Do not turn the electricity back on until all work is completed.  
2. Remove the cover and front portion of your old thermostat to  
expose the wiring connections.  
3. Write down the letters printed near each wire terminal that is  
used, and the color of the wire that is connected to it. Using the  
enclosed labels, attach a label to each of your wires so that the  
letter matches the marking on your existing thermostat.  
T
U
F
OF  
D
AY  
HEAT  
LOW BAT  
PM  
LOW BAT  
:
HEATING AND COOLING  
5 36  
72  
Basic operation of your heating or cooling system can be obtained by ensuring that  
the rotary dial is in the RUN position, and simply moving the Temperature mode  
switch to either the HEAT or COOL position. Prior to being set initially with your  
custom temperature program, and also after a Software Reset, the thermostat will  
follow the default Energy Star® approved temperature routines that are preset within  
the thermostat’s memory, as shown below.  
To replace the batteries in the thermostat,  
remove the thermostat’s body from the  
base plate attached to the wall by pressing the thumb latch at the bottom center of  
the unit and swinging the body towards you, up and away from the base. Remove  
the used batteries from the battery tray and discard appropriately.  
4. When they are all labeled, carefully remove the wires one at a time, making sure  
that they do not fall back inside the wall. Do not allow any of the bare wire ends to  
touch each other, or any parts on the thermostat.  
5. Loosen all of the screws on the old thermostat and remove it from the wall.  
Install two new Energizer® or DURACELL®, “AA” size alkaline batteries into the  
battery tray. Observe the polarity markings shown in the battery compartment to  
ensure proper installation. When finished, hang the top of the unit by the tabs at  
the top corners of the base, then snap the bottom of the unit into place. Do not use  
unnecessary force. If the body does not snap into place easily, remove the body, re-  
hang it from the tabs and try again.  
MOUNTING  
1. Strip insulation leaving 3/8 in. (9.5mm) bare wire ends and clean off any  
corrosion.  
PERIOD  
HEAT MODE  
COOL MODE  
MORN 6:00 AM 70 °F (21 °C) 6:00 AM 78 °F (26 °C)  
DAY  
EVE  
2. Fill wall opening with non-combustible insulation to prevent drafts from  
affecting the thermostat.  
8:00 AM 62 °F (17 °C) 8:00 AM 85 °F (29 °C)  
6:00 PM 70 °F (21 °C) 6:00 PM 78 °F (26 °C)  
CAUTION:  
NITE 10:00 PM 62 °F (17 °C) 10:00 PM 82 °F (28 °C)  
Be careful not to drop the unit or disturb electronic parts. Leave the door closed  
while the body is being removed from the base.  
TECHNICAL ASSISTANCE  
MINIMUM RUN TIME DELAY  
If you have any problems installing or using this thermostat, please carefully and  
thoroughly review the instruction manual. If you require assistance, please contact  
our Technical Assistance department at 856-234-8803 during regular business  
hours between 8:00AM and 4:30PM Eastern Standard Time, Monday through  
Friday. You can also receive technical assistance online anytime day or night at  
technical questions, and also permits you to email your questions to our technical  
support staff at your convenience.  
3. Remove the body from the thermostat’s base by pressing the thumb latch at the  
bottom center of the unit and swinging the body away.  
This is determined by the thermostat, and controls the minimum length of time that  
the thermostat must remain with Heat or Cool either On or Off, before it will  
automatically switch to the alternate On or Off state. This feature prevents rapid or  
short cycling, and provides compressor protection for cooling equipment. The time  
amount for this delay is fixed at 5 minutes between on or off load changes.  
NOTE:  
If you are mounting the base to soft material like plasterboard or if you are using  
the old mounting holes, the screws may not hold. Drill a 3/16 in. (4.8mm) hole at  
each screw, and insert the plastic anchors provided.  
TEMPERATURE OVERRIDE  
A Temperature Override occurs in Run mode, in either Heat or Cool, anytime the  
user adjusts the set temperature to a value that differs from the stored program  
temperature for that day and time. When the thermostat is in an Override, the word  
Override will appear in the temperature area of the display. The thermostat will  
maintain thermal control using this new set temperature, until the start of the next  
program period time is reached. At the start of the next program period, the set  
temperature will return to its programmed value. To enter an Override in either Heat  
or Cool mode, push either the UP or DOWN button once and the set temperature  
will begin to flash. Push either the UP or DOWN button to the new desired set  
temperature value. An Override may be cancelled by rotating the dial, changing the  
Temperature mode switch, or by initiating a Temperature Hold.  
4. Hold the base against the wall. Route the wires through the hole below the  
terminal block. Position the base for best appearance (to hide any marks from an  
old thermostat). Attach the base to the wall with the two screws provided.  
WARRANTY  
Limited Warranty: If this unit fails because of defects in materials or workmanship  
within three years of the date of original purchase, LUX Products Corporation will,  
at its option, repair or replace it. This warranty does not cover damage by accident,  
misuse, or failure to follow installation instructions. Implied warranties are limited  
in duration to three years from date of original purchase. Some states do not allow  
limitations on how long an implied warranty lasts, so the above limitation may not  
apply to you. Please return malfunctioning or defective units to the participating  
retailer from which purchase was made, along with proof of purchase. Please refer  
to the “TECHNICAL ASSISTANCE” section before returning thermostat. Purchaser  
assumes all risks and liability for incidental and consequential damage resulting  
from installation and use of this unit. Some states do not allow the exclusion of  
incidental or consequential damages, so the above exclusion may not apply to you.  
This warranty gives you specific legal rights and you may also have other rights  
which vary from state to state. Applicable in the U.S.A. only.  
CONNECTING THE WIRES  
5. Wires must be trapped between the black clamps and the brass  
terminals as shown here.  
6. Being careful not to overighten them, securely tighten all of the  
electrical terminal screws, including any unused ones.  
NOTE:  
TEMPERATURE HOLD  
When you are finished performing your installation and setup options, please  
remove the thin plastic film that is protecting the LCD display screen on the front of  
the thermostat. This plastic may or may not be present, and is evident by the  
appearance of fake digits appearing on the display screen.  
A Temperature Hold is similar to an override, but is used for maintaining a constant  
set temperature for a longer time duration. Once a Hold is initiated, the thermostat  
will maintain the Hold set temperature indefinitely. A temperature hold may be used  
for days, weeks, or even months at a time. To enter a Hold, push the HOLD button  
once, and the word Hold will appear in the temperature portion of the screen, along  
with the set temperature flashing. While the set temperature is flashing, push either  
the UP or DOWN button to the new desired set temperature value. To cancel a Hold,  
press and release the HOLD button once again, rotate the dial, or change the  
Temperature mode switch.  
WIRING INFORMATION  
** Complete heating and/or cooling system wiring can be found in the WIRE  
IDENTIFICATION AND WIRING SCHMATICS section of this instruction sheet. The  
schmatics shown provide component information for brand new installations or  
for unreferenced wires.  
©
2 0 0 6 L U X P R O D U C T S C O R P O R A T I O N . A L L R I G H T S R E S E R V E D  
href="
ENGLISH - WIRE IDENTIFICATION AND WIRING SCHEMATICS  
HEATING ONLY SYSTEMS  
JUMPER  
PROVIDED  
COOLING ONLY SYSTEMS  
TYPICAL 2, 3, OR 4-WIRE, 24-VOLT  
HEATING ONLY SYSTEMS  
TYPICAL 5 AND 6-WIRE, 24-VOLT  
HEATING AND COOLING SYSTEMS  
WITH TWO TRANSFORMERS  
JUMPER  
PROVIDED  
AND MILIVOLT HEATING SYSTEMS  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
W
G
F
R
Y
G
F
RH  
V
5
RC  
V
5
H
4
C*  
6
GAS  
GAS  
HEAT  
XFMR  
COOL  
XFMR  
VALVE  
OR  
A/C  
COMPRESSOR  
SYSTEM  
XFMR  
VALVE  
OR  
FAN  
FAN  
HEATER  
HEATER  
HEATING / COOLING SYSTEMS  
HEATING / COOLING SYSTEMS  
4 & 5 WIRE WITH ONE TRANSFORMER  
5 & 6 WIRE WITH TWO TRANSFORMERS  
TYPICAL 4-WIRE, 24-VOLT  
SINGLE STAGE HEAT PUMP SYSTEMS  
JUMPER  
JUMPER  
( REMOVED )  
PROVIDED  
TYPICAL 3 AND 4-WIRE, 24-VOLT  
COOLING ONLY SYSTEMS  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
Y
W
G
F
RH RC  
Y
W
G
F
RH  
RC  
V
C*  
6
H
4
V
R
R
5
C*  
6
H
4
5
SYSTEM  
XFMR  
A/C  
COMPRESSOR  
HEAT  
PUMP  
UNIT  
FAN  
REVERSING  
VALVE  
SYSTEM  
XFMR  
FAN  
TYPICAL SINGLE STAGE  
HEAT PUMP WIRING  
WIRING DIAGRAM NOTES:  
RC-RH JUMPER  
*CUSTOMER  
SUPPLIED  
JUMPER  
TYPICAL 4 AND 5-WIRE, 24-VOLT  
HEATING AND COOLING SYSTEMS  
WITH ONE TRANSFORMER  
PROVIDED  
• All of the dashed wires are optional, and usage depends upon your specific  
system type. Use either the “B” or the “O” wire, but not both. Generally, the B  
and O terminals are only used for Heat Pump systems.  
• If replacing a Honeywell TM-11, tape off the “R” wire. Connect the “B” wire  
to the “RH” terminal.  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
Y
G
F
O
B*  
• If replacing a thermostat that has a clock wire labeled as “C,” tape off this  
wire and do not connect it to this thermostat.  
RC  
RH  
V
• If “Y” and “C” wires are both present, then “C” is a common wire, do not  
connect it to this thermostat.  
• If a “B” wire in your system is a common wire, connecting it to the “B”  
terminal of this thermostat may damage your system and the thermostat, tape it  
off and do not connect it.  
C*  
6
GAS  
5
SYSTEM  
XFMR  
VALVE  
OR  
A/C  
COMPRESSOR  
FAN  
HEATER  
USE "B" OR "O"  
NOT BOTH  
FRANÇAIS – IDENTIFICATION DES FILS ET SCHÉMAS DE CÂBLAGE  
SYSTÈMES DE CHAUFFAGE ET DE  
CLIMATISATION DE 24 VOLTS À 5 OU 6 FILS  
AVEC DEUX TRANSFORMATEURS  
SYSTÈMES DE CHAUFFAGE SEUL  
SYSTÈMES DE CLIMATISATION SEULE  
SYSTÈMES DE CHAUFFAGE SEUL  
DE 24 VOLTS À 2, 3 OU 4 FILS ET  
SYSTÈMES DE CHAUFFAGE À MINIVOLTS  
CAVALIER FOURNI  
CAVALIER FOURNI  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
W
G
F
R
Y
G
F
RH  
V
5
RC  
V
5
H
4
C*  
6
TRANSFORMATEUR  
CHAUFFAGE  
COMPRESSEUR  
C.A.  
ROBINET DE GAZ  
OU APPAREIL  
DE CHAUFFAGE  
VENTILATEUR  
TRANSFORMATEUR  
SYSTÈME  
VENTILATEUR  
ROBINET DE GAZ  
OU APPAREIL  
DE CHAUFFAGE  
TRANSFORMATEUR  
CLIMATISATION  
SYSTÈMES DE CHAUFFAGE/CLIMATISATION  
SYSTÈMES DE CHAUFFAGE/CLIMATISATION  
4 OU 5 FILS ET UN TRANSFORMATEUR  
5 OU 6 FILS ET DEUX TRANSFORMATEURS  
SYSTÈMES DE CLIMATISATION SEULE  
DE 24 VOLTS À 3 OU 4 FILS  
CAVALIER FOURNI  
(CAVALIER RETIRÉ)  
SYSTÈMES À POMPE DE CHAUFFAGE  
MONOÉTAGÉE DE 24 VOLTS À 4 FILS  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
Y
W
G
F
RH RC  
Y
W
G
F
RH  
RC  
V
C*  
6
H
4
V
R
R
5
C*  
6
H
4
5
TRANSFORMATEUR  
SYSTÈME  
COMPRESSEUR C.A.  
VENTILATEUR  
POMPE DE  
CHAUFFAGE  
TRANSFORMATEUR  
SYSTÈME  
ROBINET  
D’INVERSION  
VENTILATEUR  
CÂBLAGE POUR POMPE DE CHALEUR MONOÉTAGÉE  
*CAVALIER  
FOURNI  
CAVALIER RC-RH  
FOURNI  
SYSTÈMES DE CHAUFFAGE ET DE  
CLIMATISATION DE 24 VOLTS À 4 OU 5 FILS  
AVEC UN TRANSFORMATEUR  
NOTES SUR LES SCHÉMAS DE CÂBLAGE :  
PAR LE CLIENT  
• Tous les fils pointillés sont optionnels; leur présence dépend du système  
installé. Utiliser « B » ou « O », mais non les deux. En règle générale, les bornes  
B et O sont utilisées uniquement avec les systèmes à pompe de chauffage.  
• Si le thermostat remplacé était un Honeywell TM-11, ne pas raccorder le fil R  
et le recouvrir de ruban électrique. Raccorder le fil B à la borne RH.  
• Si le thermostat remplacé comportait un fil d’horloge étiqueté C, ne pas  
raccorder le fil C au thermostat et le recouvrir.  
• Si les fils Y et C sont tous deux présents, le fil C est un fil commun. Ne pas le  
raccorder au thermostat.  
• Si dans votre système le fil B est le fil commun, le fait de le raccorder à la  
borne B de ce thermostat peut endommager le système et le thermostat. Ne pas  
le raccorder et le recouvrir.  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
Y
G
F
O
B*  
RC  
RH  
V
C*  
6
5
ROBINET DE GAZ  
OU APPAREIL  
DE CHAUFFAGE  
TRANSFORMATEUR  
SYSTÈME  
COMPRESSEUR  
C.A.  
VENTILATEUR  
UTILISER « B » OU « O »,  
MAIS NON LES DEUX  
ESPAÑOL – IDENTIFICACION DE CABLES Y DIAGRAMAS DE CABLEADO  
SISTEMAS DE CALEFACCION  
SOLAMENTE  
SISTEMAS DE AIRE ACONDICIONADO  
SISTEMAS TIPICOS DE CALEFACCION  
SOLAMENTE  
SE INCLUYE LA CONEXION DE PUENTE  
SISTEMAS TIPICOS DE CALEFACCION SOLAMENTE  
DE 24 VOLTIOS DE 2, 3 O 4 ALAMBRES  
Y SISTEMAS DE CALEFACCION DE MILIVOLTIOS  
Y AIRE ACONDICIONADO DE 24 VOLTIOS  
DE 5 Y 6 ALAMBRES CON DOS TRANSFORMADORES  
SE INCLUYE LA CONEXION DE PUENTE  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
W
G
F
R
Y
G
F
RH  
V
5
RC  
V
5
COMPRESOR  
DE AIRE  
ACONDICIONADO  
H
4
C*  
6
XFMR DE  
CALEFACCION  
CALENTADOR  
O VALVULA  
DE GAS  
VENTILADOR  
XFMR DEL  
SISTEMA  
VENTILADOR  
CALENTADOR  
O VALVULA  
DE GAS  
XFMR DE AIRE  
ACONDICIONADO  
SISTEMAS DE CALEFACCION/  
AIRE ACONDICIONADO  
SISTEMAS DE CALEFACCION/  
AIRE ACONDICIONADO  
4 Y 5 ALAMBRES CON UN TRANSFORMADOR  
5 Y 6 ALAMBRES CON DOS TRANSFORMADORES  
SISTEMAS TIPICOS DE AIRE ACONDICIONADO  
SOLAMENTE DE 24 VOLTIOS DE 3 Y 4 ALAMBRES  
SISTEMAS TIPICOS DE BOMBA DE CALOR  
DE UNA FASE DE 24 VOLTIOS DE 4 ALAMBRES  
(CONEXION DE PUENTE RETIRADA)  
SE INCLUYE LA CONEXION DE PUENTE  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
R
Y
W
G
F
RH RC  
Y
W
G
F
RH  
RC  
V
C*  
6
H
4
V
R
R
5
C*  
6
H
4
COMPRESOR  
DE AIRE  
ACONDICIONADO  
XFMR DEL  
SISTEMA  
5
VENTILADOR  
UNIDAD DE  
LA BOMBA  
DE CALOR  
XFMR DEL  
SISTEMA  
VALVULA  
DE 4 VIAS  
VENTILADOR  
CABLEADO TIPICO DE UNA BOMBA DE CALOR DE UNA FASE  
NOTAS SOBRE LOS DIAGRAMAS DE CABLEADO:  
SISTEMAS TIPICOS DE CALEFACCION  
Y AIRE ACONDICIONADO DE 24 VOLTIOS  
DE 4 Y 5 ALAMBRES CON UN TRANSFORMADOR  
SE INCLUYE CONEXION  
DE PUENTE RC-RH  
*CONEXION DE PUENTE  
PROVISTA POR EL CLIENTE  
• Todos los alambres de trazo discontinuo son opcionales y el uso depende del tipo  
de su sistema específico. Use el alambre “B” o el “O”, pero no ambos.  
Generalmente, los terminales B y O se usan solamente para sistemas de bombas de  
calor.  
RH RC  
Y
W
G
O
B
RH RC  
Y
W
G
O
B
• Si va a reemplazar un Honeywell TM-11, coloque cinta sobre el alambre “R”.  
Conecte el alambre “B” al terminal “RH”.  
• Si va a reemplazar un termostato que tiene un alambre para el reloj marcado con  
una “C”, coloque una cinta sobre este alambre y no lo conecte a este termostato.  
• Si existen los dos alambres “Y” y “C”, entonces “C” es un alambre común, no lo  
conecte a este termostato.  
• Si el alambre “B” de su sistema es un alambre común, conectarlo al terminal “B”  
de su termostato puede dañar su sistema y el termostato, coloque una cinta sobre  
el mismo y no lo conecte.  
R
Y
G
F
O
B*  
RC  
RH  
V
C*  
6
CALENTADOR  
O VALVULA  
DE GAS  
COMPRESOR  
DE AIRE  
ACONDICIONADO  
XFMR DEL  
SISTEMA  
VENTILADOR  
5
USE “B” U “O” PERO NO AMBOS